How to Choose the Right Servo Stabilizer Size (kVA Guide)

Short answer: add up the connected load in kVA, add 20–30% for motor starting and future machines, and choose a stabilizer whose input range covers the lowest and highest voltage your site actually sees.

Step 1: Calculate the load

List every machine the stabilizer will feed. If nameplates show kW, convert to kVA by dividing by the power factor (typically 0.8): kVA = kW ÷ 0.8. Add them up.

Step 2: Add margin

Motors draw several times their running current at start. Add 20–30% headroom, more if large motors start together. Example: 40 kVA of machines → choose about 50 kVA.

Step 3: Know your voltage range

Measure or note the lowest and highest supply voltage across the day and season. The stabilizer's input range must cover it. A narrower range than your site's swing means the stabilizer cannot fully correct.

Step 4: Single phase or three phase

Single-phase stabilizers suit individual machines and offices. A three-phase stabilizer protects a full plant or three-phase machines. On three-phase supply with unbalanced voltages, ask for independent phase correction.

What else matters

  • Correction speed – how fast it reacts (Unitech: up to 50 V/s)
  • Efficiency – losses run all day (Unitech: up to 97%)
  • Generator compatibility if you run on DG
  • Service – carbon brushes and variacs need periodic checks

Unsure? Share your load list and voltage readings and a Unitech engineer will recommend the rating. See our servo stabilizers.